
Page - 52/73 AESZP0BA – AC1 SSL SENSORED - FREE VERSION - User Manual
QUICK INVERSION reading becomes ON when the Exclusive Hydro
Microswitch switch closes and connects the CNB#7 input to a key
voltage.
22) CUTBACK SWITCH 2
(Standard version only). ON/OFF. This is the level of the CNA#14 digital
input (When the MDI-PRC is not present, and SET INPUT #2 is set
PRESENT, this is the Speed Reduction #2 request):
- ON GND = When CNA#14 is not closed to a battery (key) voltage (or
connected to GND) the SR#2 request is active.
- OFF +VB = When CNA#14 is closed to a battery (key) voltage the
SR#2 request is not active.
This input CNA#14 has the alternative function of Inching Forward request
when the SET INPUT #2 is set to OPTION#1. Then the Inching Forward
request turns active (meanwhile this CUTBACK SWITCH 2 reading turns
ON) when the CNA#14 closes to a battery (key) voltage.
23) CUTBACK SWITCH 3
(Standard versione only). ON/OFF. This is the level of the CNA#15 digital
input (When the MDI-PRC is not present, and the SET INPUT #3 is set
PRESENT, this is the Speed Reduction #3 request):
- ON GND = When CNA#15 is not closed to a battery (key) voltage (or
connected to GND) the SR#3 request is active.
- OFF +VB = When CNA#15 is closed to a battery (key) voltage the
SR#3 request is not active.
This input CNA#15 has the alternative function of Inching Backward request
when the SET INPUT #3 is set to OPTION#1. Then the Inching Backward
request turns active (meanwhile this CUTBACK SWITCH 3 reading turns
ON) when the CNA#15 closes to a battery (key) voltage.
24) LIFTING CONTROL
(MDI-PRC Version only). From 0.0V to 5.0V. When the MDI-PRC is present,
the potentiometer connected to CPOTB on CNA#18 is used for a proportional
control of the hydraulics. The voltage on the wiper of this potentiometer
(CNA#18) is halved inside the controller and then recorded on this reading.
That means the actual wiper voltage is in the range 0 to 10V meanwhile the
corresponding LIFTING CONTROL reading is in the range 0.0 to 5.0Vdc.
25) DIGITAL INPUT #1
(MDI-PRC version only). ON/OFF. This is the level of the CNA#14 digital
input (when the MDI-PRC is present this input is an Auxiliary (2
nd
) Lifting
request):
- ON +VB = When CNA#14 is closed to a battery (key) voltage the
Aux Lifting request is active.
- OFF GND = When CNA#14 is not closed to a battery (key) voltage (or
it is connected to GND) the Aux Lifting request is not
active.
26) DIGITAL INPUT #2
(MDI-PRC version only). ON/OFF. This is the level of the CNA#15 digital
input (when the MDI-PRC is present this input is an Auxiliary (2
nd
) Lowering
request):
- ON +VB = When CNA#15 is closed to a battery (key) voltage the
Aux Lowering request is active.
Kommentare zu diesen Handbüchern